Functions
Leuze electronic GmbH + Co. KG RSL 420P 42
• The changeover time starts when the safety sensor registers a change at control inputs F1 to F5. When
the changeover time has expired, only one field pair should still be active.
• Monitoring of the newly activated field pair starts when the changeover time has expired.
• The changeover time is specified with the configuration and diagnostics software (see chapter 9.4.4
"Creating and configuring protective/warning field pairs").
Tab.5.5: Connection of control inputs F1 to F5 with activation of field pairs A1.1 to A1.10 for protective function A
Field pair Control input Description
F1 F2 F3 F4 F5
A1.1 1 0 0 0 0 Field pair A1.1 is active
A1.2 0 1 0 0 0 Field pair A1.2 is active
A1.3 0 0 1 0 0 Field pair A1.3 is active
A1.4 0 0 0 1 0 Field pair A1.4 is active
A1.5 0 0 0 0 1 Field pair A1.5 is active
A1.6 1 1 1 1 0 Field pair A1.6 is active
A1.7 1 1 1 0 1 Field pair A1.7 is active
A1.8 1 1 0 1 1 Field pair A1.8 is active
A1.9 1 0 1 1 1 Field pair A1.9 is active
A1.10 0 1 1 1 1 Field pair A1.10 is active
In the case of two protective functions, connection of control inputs F6 to F10 applies analogously for acti-
vation of field pairs B1.1 to B1.10 for protective function B.
2 3 4
PF1.1
PF1.2
PFA…
PFA.x
1
5
7
6
0 0
1
A1.2
0
0 0
1 1
1
XX
0 1
1 1
0
00 0
A1.2 A1.x
0
0
0
0
0
1
1 Active protective field
2 An old protective field is active
3 Set changeover time
4 A new protective field is active
5 Initiation of the field pair changeover caused by a change in the signal – the old protective field is monitored
until the end of the changeover time
6 Fixed end – field pair changeover complete
7 …Only one field pair change
PF Field pair
XX Field pair changeover
Fig.5.2: Signal/time diagram: Overlapped monitoring