Installation
53GA02411_002_C0 - 10/2016 - © Leybold
The failure messaging output S2 is active (low) until being reset. The warning
messaging output S1 remains active as long as the warning threshold is
exceeded (no saving of the status).
During the start-up phase of the pump, the sensor signals are processed dif-
ferently so that displayed values may exceed the parameter values stated in
the table.
Parameter values
Parameter Default settings Unit Description
SP 630 SP 630 F
a 100 100 digits Warning limit, vibrations
b 150 150 digits Failure limit, vibrations
c 10 10 0,2 s Hysteresis, vibration meas.
d 80 60 °C Warning limit, oil temperature
Failure limit for
ATEX operation
e 90 70 °C Failure limit, oil temperature
for non-ATEX operation
o 20 20 digits “Pump on” threshold
switch logic = off (default)
Status Table for the Switching Outputs
Outputs
Designation Warning Failure Pump on Watchdog
Abbreviation S1 S2 S4 S3
Plug contact 12 13 15 14
Status Status
Failure/Warning Rotor
-/- standstill high high high hi-lo-hi (1s)
-/- turning high high low hi-lo-hi (1s)
Warning level
exceeded low low high high hi-lo-hi (1s)
Warning level
exceeded turning low high low hi-lo-hi (1s)
Filure level
exceeded standstill low low high hi-lo-hi (1s)
Filure level
exceeded turning low low low hi-lo-hi (1s)