Installation
28
GA05118_002_C1 - 11/2017 - © Leybold
30
°C
45
40
35
30
25
20
°C
20 %
50 %
100 %
90 %
70 %
80 %
60 %
30 % 40 %
510152025
Minimum coolant inlet temperature at
which condensation does not yet occur,
as a function of maximum room tempe-
rature and maximum relative humidity.
Example:
Max. ambient temperature 25 °C
Min. coolant inlet temperature 17 °C
Max. relative humidity 60%
Maximum relative humidity
Maximum ambient temperature
Minimum coolant inlet temperature
Fig. 3.6 Dewpoint diagram