System Set-Up
60
Summary
Example of Fuction Code Display
Function Code Value #1 Value #2
Function Default Value #1 Value #2 Remark
Disable 3 Min. Delay 02:01 01 -
Remote Air Sensor Connection 03:01
01 : NOT connected.
02 : connected.
-
Celsius/Fahrenheit Switching 04:01
01 : Celsius
02 : Fahrenheit
-
Setting Temp. Selection 05:02
01 : Air Temp.
02 : Leaving water Temp.
-
Auto Dry Contact 06:01
01 : Auto Start OFF
02 : Auto Start ON
-
Address Setting 07:00 00 ~ FF -
Override Setting 08:00
00 : Slave
01 : Master
-
Water Pump Test Run 09:00 01 : Set
Setting Air Temp.
(Heating Mode)
13:030:016
24℃(75℉) ~ 30℃(86℉)
: Upper Limit of setting range
16℃(60℉) ~ 22℃(71℉)
: Lower Limit of setting range
Setting Leaving Waer Temp.
(Heating Mode)
14:080:046
50℃(122℉) ~ 80℃(176℉)
: Upper Limit of setting range
30℃(86℉) ~ 46℃(114℉)
: Lower Limit of setting range
Setting Sanitary Tank Water Temp.
(Sanitary Water Heating)
15:080:046
50℃(122℉) ~ 80℃(176℉)
: Upper Limit of setting range
30℃(86℉) ~ 46℃(114℉)
: Lower Limit of setting range
Setting outdoor Temp. range
(Weather-dependent operation)
23:-10:015
10℃(50℉) ~ 20℃(68℉)
: Upper Limit of setting range
-20℃(-4℉) ~ 05℃(41℉)
: Lower Limit of setting range
Setting indoor air Temp. range
(Weather-dependent operation)
24:021:016
20℃(68℉) ~ 30℃(86℉)
: Upper Limit of setting range
16℃(60℉) ~ 19℃(66℉)
: Lower Limit of setting range
Setting leaving water Temp.
(Weather-dependent operation)
25:080:046
65℃(149℉) ~ 80℃(176℉)
: Upper Limit of setting range
40℃(104℉) ~ 54℃(129℉)
: Lower Limit of setting range
Setting start/maintain time
(Disinfection Operation)
26:000
00 : Disable
01 : Enable
-
26:006:023
01~07 : Starting Date
(01:Sun, 02:Mon, ····, 07:Sat)
00~23 hours
: Starting Time in 24 hours
Setting Temp.
(Disinfection Operation)
27:070:010
40℃(104℉) ~ 70℃(129℉)70
: Maximum heating Temp.
05~60 min
: Maximum heating duration
Setting control parameter
(Sanitary water heating operation)
28:005:080
01℃(33℉) ~ 20℃(68℉)
: Temp. gap from Value #2
50℃(122℉) ~ 80℃(176℉)
Setting control parameter
(Sanitary water heating operation)
29:003:000 02℃(35℉) ~ 04℃(39℉) 00~01
Setting sanitary water heating timers
2b:030 5 ~ 95 min (step: 5 min) -
2b:180:020 0 ~ 600 min (step: 30 min) 20 ~ 95 min (step: 5 min)
Changing thermal on/off room air Temp.
2E:00 00~03 -
Changing thermal on/off leaving water
Temp.
2F:00 00~03 -
Program version 30:*** Display Version number -
Changing thermal on/off sanitary tank
water Temp.
33:00 00~03 -
Select entering/leaving water Temp mode
in Heating Mode
34:00
00 : Based on leaving water Temp
01 : Based on entering water Temp
-
Water Pump operation/delay time set
in Heating Mode
37:000:001
000: Operates according to OFF time setting
001 : Pump always on
001 ~ 060 : OFF Time (minutes)
Forced product operation 39:00
00 : Forced product operation in use
01 : Forced product operation not in use
Dry Contact installation set 41:00
00 : Dry Contact equipped decided on
01 : Dry Contact not installed
02 : Dry Contact installed
*Temp. = Temperature