System Set-Up
64
• Function Code 26 and 27 : Setting Disinfection operation
Disinfection operation is special sanitary tank operation mode to kill and to prevent growth of
viruses inside the tank.
- Value #1 of Function Code 26 : Selecting disinfection operation mode. ‘00’ for setting disinfection
mode off, and ‘01’ for setting disinfection mode on.
- Value #2 of Function Code 26 : Determining the date when the disinfection mode is running. ’01’
for Sunday, ’02’ for Monday, … , and ’06’ for Saturday.
- Value #3 of Function Code 26 : Determining the time when the disinfection mode is running. ’00’
for 0:00am, ’01’ for 01:00am, … , ’22’ for 10:00pm, and ’23’ for 11:00pm.
- Value #1 of Function Code 27 : Target temperature of disinfection mode.
- Value #2 of Function Code 27 : Duration of disinfection mode.
WARNING
Vales of Function Code 26
• If Value #1 of Function Code 26 is set as ’00’, Value #2 and Value #3 is not used.
• When Value #1 is set as ’01’, Value #2 is displayed at the position of Value #1 and Value #3 is
displayed at the position of Value #2 due to limited width of the control panel display.
CAUTION
Sanitary water heating should be enabled
• If sanitary water heating is disabled, the disinfection mode
will not be operated although Value #1 of Code 26 is set
as ’01’.
• To use disinfection mode, sanitary water heating should
be enabled.
Time
Value #2 of
Function Code 26
Value #1 of
Function Code
27
Value #2 of
Function Code 27
Water temperature
(Inside sanitary water tank)
Temperature profile
of Disinfection operation
Press repeatedly Button to enable sanitary
tank heating
<Sanitary Water Heating Disable>
<Sanitary Water Heating enable>