Service Manual 205
Troubleshooting Guide
10) Troubleshooting CH32, CH33
LEV Openness
(Pulse)
COMP Frequency
(Hz)
Toff(105) °C
T1(90) °C
T2(95) °C
OFFNormal
OFF ControlNormal
Normal
Normal
D-Pipe temp.
32
33
D-pipe (Inverter)
temp. high
(105°C )
D-pipe (Constant)
temp. high
(105°C )
Discharge sensor
(Inverter) temp. high
Discharge sensor
(Cons.) temp. high
Check the discharge pipe sensor for INV.
Check the install condition for over load.
Check the leakage of refrigerant.
Check the SVC V/V open.
Check the discharge pipe sensor for Cons.
Check the install condition for over load.
Check the leakage of refrigerant.
Check the SVC V/V open.
Display
code
Title Cause of error Check point & Normal condition
Check Point
CH 32
1. Check the install condition for over load.
2. Check the SVC V/V open.
3. Check the leakage of refrigerant.
CH 33
1. Check the install condition for over load.
2. Check the SVC V/V open.
3. Check the leakage of refrigerant.
4. Check the constant compressor. (same with CH21)

Table of Contents

Other manuals for LG AMNH07GD4L0

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LG AMNH07GD4L0 and is the answer not in the manual?

LG AMNH07GD4L0 Specifications

General IconGeneral
BrandLG
ModelAMNH07GD4L0
CategoryAir Conditioner
LanguageEnglish

Related product manuals