Date:
JobName/Location:
PONo.:
Architect:
Engr:
GC:
Rep:
For:
File
A
roval
Mech:
Resubmit
Other
Tag#:
(Company)
(ProjectManager)
LMN096HVT
FlexMulti‐SplitStandard
Btu/hIndoorUnit9,000
Performance:
NominalCapacity(Btu/h) 9,000
CoolingNominalTestConditions: HeatingNominalTestConditions:
Indoor:
80°FDB/67°FWB Indoor: 70°FDB/60°FWB
Outdoor:
95°FDB/75°FWB Outdoor: 47°FDB/43°FWB
Electrical:
PowerSupply(V/Hz/Ø) 208‐230/60/1
RatedAmps(A)
0.20
Pi
in
:
LiquidLine(in,OD) 1/4
VaporLine(in,OD)
3/8
ControlsFeatures:
•4‐Wayautoswing
•24‐Houron/offmer
•Autooperaon
(artificialintelligence)
•Autorestart
•Chaoswind
•Inverter
(variablespeedfan)
•JetCool/JetHeat
•Plasmaairpurifyingsystem
•Self‐cleaningindoorcoil
•Sleepmode
O
tionalAccessories:
PI485‐PMNFP14A0
ACSmartII‐PQCSW320A1E
ACPwithoutDIgitalI/O‐PQCPA11A03
ACPwithDigitalI/O‐PQCPB11A0E
LonWorksGateway‐PQNFB16A1
BACnetGateway‐PQNFB17B0
DrainOD,ID(in)
13/16,5/8
TemperatureSensor
Thermistor
MaxLengthEachPipe(ft)
82
MaxElevationbetweenODUandIDU(ft)
49.2
MaxElevationbetweenIDUandIDU(ft)
24.6
Enterin
MixedAir:
Cooling(°FDB) 54‐73
Heating(°FDB)
61‐86
UnitData:
RefrigerantType R410A
RefrigerantControl:
EEV
SoundPressureH/M/L(±3dB(A))
33/30/27
PrimaryFilter
WashablePre‐filter
SecondaryFilter
Plasma
NetUnitWeight(lbs)
24.5
ShippingWeight(lbs)
26.4
CommunicationCable(NoxAWG)
4x18
Fan:
Type CrossFlow
Quantity
1
Motor/Drive
BrushlessDigitallyControlled/Direct
AirflowRateH/M/L(CFM)
247/230/212
StandardFeatures:
•LimitedWarrantywithLGCerfiedInstallaon
•LimitedTwoYearFunconalPartsWarranty
DehumidificationRate(pts/h) 2.3
Notes:
1.SeeEngineeringManualforsensibleandlatentcapacies.
2.SoundPressurelevelsaretestedinananechoicchamberunderISOStandard1996.
3.Allcommunicaoncabletobeminimum18AWG,2‐conductor,stranded,shieldedand
mustcomplywithapplicablelocalandnationalcode.
4.Powerwiringcablesizemustcomplywiththeapplicablelocalandnaonalcodes.
5.Thisunitcomeswithadrynitrogencharge.
6.Thisdataisrated0abovesealevel,with24.6ofrefrigerantlineperindoorunitand
a0ftleveldifferencebetweenoutdoorandindoorunits.Allcapacitiesarenetwitha
combinationratiobetween95–105%.
7.MustfollowinstallaoninstruconsintheapplicableLGinstallaonmanual.
Page1of2DFS‐SB‐AD‐018‐US012M17
Forcontinualproductdevelopment,LGreservestheright tochangespecificationswithoutnotice.
LGElectronicsU.S.A.,Inc.,EnglewoodCliffs,NJ.Allrightsreserved.“LGLife’sGood”isaregisteredtrademark
ofLGCorp./www.lg‐dfs.com
PQWRHDF0
7‐DayProgrammableController(Black)‐PQRCVSL0
SimpleControllerwithMode(Black)‐PQRCVCL0Q
SimpleControllerwithoutMode(Black)PQRCHCA0Q
7‐DayProgrammableController(White)‐PQRCVSL0QW
SimpleControllerwithMode(White)‐PQRCVCL0QW
SimpleControllerwithoutMode(White)‐PQRCHCA0QW