128 | LOW STATIC
MULTI V Ducted Indoor Unit Engineering Manual
Due to our policy of continuous product innovation, some specications may change without notication.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
DUCTED LOW STATIC
Electrical Data
Table 89: Ducted Low Static (L1, L2, L3 Frames) Indoor Unit Electrical Data.
Model
Voltage
Range
MCA MOP
Rated
Amps (A)
Power Supply Power Input
1
(W)
Hz Volts Phase
Max.
Cooling
Max.
Heating
L / M / H at Factory Default
L1 Units
ARNU073L1G4
208-230
0.5
15
0.4
60 208-230 1
40 40 24 / 28 / 31
ARNU093L1G4 0.5 0.4 40 40 24 / 29 / 39
L2 Units
ARNU123L2G4
208-230
1.0
15
0.76
60 208-230 1
85 85 29 / 34 / 41
ARNU153L2G4 1.0 0.76 85 85 34 / 41 / 56
ARNU183L2G4 1.0 0.76 85 85 41 / 56 / 71
L3 Units
ARNU243L3G4 208-230 1.2 15 0.97 60 208-230 1 115 115 48 / 63 / 103
MCA : Minimum Circuit Ampacity.
MOP : Maximum Overcurrent Protection.
Units are suitable for use on an electrical system where voltage supplied to unit terminals is within the listed range limits.