EasyManua.ls Logo

LG AS-S24AC ST0 - Piping Length and Elevation Data

LG AS-S24AC ST0
89 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
80 2005 Product Data
9. Coefficient of Capacity Change
(A)
(A)
Indoor
Indoor
Outdoor
Outdoor
Classification
Height
(A)
The Coefficient of Capacity Change
Total Pipe Length(m)
5 7.5 10 12.5 15
- - - 0.94 0.93
- 0.97 0.96 0.95 0.94
0.99 0.98 0.97 0.96 0.95
1.0 0.99 0.98 0.97 0.96
1.0 0.99 0.98 0.97 0.96
0.99 0.98 0.97 0.96 0.95
- 0.97 0.96 0.95 0.94
- - - 0.94 0.93
10
7
5
0
0
5
7
10
Model: 18K~24K Btu Heat Pump
Capacity
(Btu/h)
7k~12k
3/8"(Ø9.52)
1/2"(Ø12.7)
1/2"(Ø12.7)
5/8"(Ø15.88)
5/8"(Ø15.88)
5/8"(Ø15.88)
3/4"(Ø19.05)
1/4"(Ø6.35)
1/4"(Ø6.35)
1/4"(Ø6.35)
1/4"(Ø6.35)
3/8"(Ø9.52)
3/8"(Ø9.52)
3/8"(Ø9.52)
4 or 7.5
4 or 7.5
4 or 7.5
4 or 7.5
4 or 7.5
7.5
7.5
7
7
15
15
15
15
15
15
15
30
30
30
30
30
20
20
20
20
30
30
50
18k~24k
30k~36k
Pipe Size
Gas Liquid
Standard
Length
(m)
Max.
Elevation
B (m)
Max.
Length
A (m)
Additional
Refrigerant
(g/m)
Piping length and elevation

Related product manuals