Electrical Data
54 Universal System Air Conditioner
NOTES :
1. Voltage Range
Units are suitable for use on electrical system where voltage supplied to unit terminals is not below or above listed range limits.
2. Maximum allowable voltage unbalance between phase is 2%.
3. MCA/MFA
MCA = 1.25 x Max. RLA + other RLA + each FLA
MFA = 2.25 x Max. RLA + other RLA + each FLA
( Next lower standard fuse rating. Minimum 20A)
4. Select wire size based on the MCA
5. MFA is used to select the circuit breaker and ground fault circuit interrupter(each leakage circuit breaker).
6. RLA is based on the following conditions.
Indoor temperature : 27°CDB / 19.0°CWB(80.6°FDB / 66.2°FWB)
Outdoor temperature : 35°CDB(95°FDB)
ATNC186ELAA AUUC186A/AB 220~240-1-50 7.1 32.3 1.0 0.7 10.6 20
ATNC186ELCA 220~240-1-50 7.1 1.0 10.6 20
ABNC186HLAA 220~240-1-50 7.8 1.2 11.6 20
AVNC186BLAA 220~240-1-50 8.1 0.3 11.1 20
ATNH186ELAA AUUH186A/AB 220~240-1-50 6.9 32.3 1.0 0.7 10.3 20
ATNH186ELCA 220~240-1-50 6.9 1.0 10.3 20
ABNH186HLAA 220~240-1-50 7.4 1.2 11.1 20
AVNH186BLAA 220~240-1-50 7.7 0.3 10.6 20
ATNC246FLAA AUUC246A/AB 220~240-1-50 9.7 62 0.7 0.7 13.6 20
ATNC246FLCA 220~240-1-50 9.7 0.7 13.6 20
ABNC246HLAA 220~240-1-50 10.1 1.2 14.5 20
AVNC246BLAA 220~240-1-50 198V 264V 10 0.4 13.6 20
ATNH246FLAA AUUH246A/AB 220~240-1-50 9.6 62 0.7 0.7 13.4 20
ATNH246FLCA 220~240-1-50 9.6 0.7 13.4 20
ABNH246HLAA 220~240-1-50 9.9 1.2 14.2 20
AVNH246BLAA 220~240-1-50 10.1 0.4 13.7 20
ATNC306FLAA AUUC306A/AB 220~240-1-50 11.4 68 0.9 0.7 15.8 25
ATNC306FLCA 220~240-1-50 11.4 0.9 15.8 25
ABNC306GLAA 220~240-1-50 11.9 1.7 17.3 25
AVNC306BLAA 220~240-1-50 12.1 0.5 16.3 25
ATNH306FLAA AUUH306A/AB 220~240-1-50 11.8 68 0.9 0.7 16.3 25
ATNH306FLCA 220~240-1-50 11.8 0.9 16.3 25
ABNH306GLAA 220~240-1-50 12.2 1.7 17.6 25
AVNH306BLAA 220~240-1-50 12.3 0.5 16.6 25
ATNC368DLAA AUUC368A/AB 380~415-3-50 4.9 47 1 0.9 8.1 20
ATNC368DLCA 380~415-3-50 4.9 1 8.1 20
ABNC368GLAA 380~415-3-50 5.2 1.8 9.2 20
ATNH368DLAA AUUH368A/AB 380~415-3-50 4.9 47 1 0.9 8.1 20
ATNH368DLCA 380~415-3-50 4.9 1 8.1 20
ABNH368GLAA 380~415-3-50 5.2 1.8 9.2 20
ATNC488DLAA AUUC488A/AB 380~415-3-50 6.5 63 2 1.6 11.8 20
ATNC488DLCA 380~415-3-50 6.5 2 11.8 20
ABNC488ELAA 380~415-3-50 342V 456V 6.8 3.8 13.9 20
ATNH488DLAA AUUH488A/AB 380~415-3-50 6.5 63 2 1.6 11.8 20
ATNH488DLCA 380~415-3-50 6.5 2 11.8 20
ABNH488ELAA 380~415-3-50 6.8 3.8 13.9 20
ATNC608DLAA AUUC608A/AB 380~415-3-50 6.9 81 2.3 1.6 12.7 25
ATNC608DLCA 380~415-3-50 6.9 2.3 12.7 25
ABNC608ELAA 380~415-3-50 7.9 3.8 15.3 25
ATNH608DLAA AUUH608A/AB 380~415-3-50 6.9 81 2.3 1.6 12.7 25
ATNH608DLCA 380~415-3-50 6.9 2.3 12.7 25
ABNH608ELAA 380~415-3-50 7.9 3.8 15.3 25
Nominal
Capacity
(Btu/hr)
Indoor Unit Outdoor Unit V-PH-Hz
OperatingVoltage Compressor
Indoor
Ooutdoor
Power
Minimum Maximum
RLA Fan FLA
Fan FLA LRA
MCA MFA
18k
24k
30k
36k
48k
60k
Electrical Data