External Static Pressure & Air Flow
Service Manual 57
2. Ceiling Concealed Duct (ABNC-HL/GL, ABNH-HL/GL Models)
(1) Open the rear cover of the wired remote-controller to set the mode.
(2) Select one of three selectable modes as follows.
■ Without Zone System
1. Position V-H, F-H:
• This position sets the maximum E.S.P as a default set.
2. Position V-L:
• This position sets the minimum E.S.P as a default set.
■ With Zone System
1. Position V-H:
• Maximum E.S.P setting & Fan speed is varied according to the state of dampers by micom.
2. Position F-H:
• Maximum E.S.P setting & Fan speed doesn't vary according to the opening & Closing of dampers.
3. Position V-L:
• Minimum E.S.P setting & Fan speed is varied according to the state of dampers by micom.
*Maximum: 18/24K-8mmAq
30/36K-10mmAq
Minimum: All-0mmAq
(3) Move the slide switch to set position.
(4) Close the rear cover and check if it works normally.
• Select the position after checking duct work and E.S.P of the unit.
• Maunfactured in the position F-H.