E.S.P. setting value (reference)
[ Notes ]
1. To get the desired Airflow & E.S.P. combination from the table set the matching value from the table. Value other than
that in table will not give the combinations of airflow & E.S.P. which are mentioned in the table.
2. Table data is based at 230V. According to the fluctuation of voltage, air flow rate varies.
Table 1
Part 2 Functions & Controls
Setting Value
Static Pressure[mmAq(Pa)]
2.5(25) 4(39) 6(59) 8(78)
100 12.8 - - -
105 13.9 - - -
110 15.2 12.7 - -
115 16.5 14.0 - -
120 17.8 15.3 12.7 -
125 - 16.5 14.0 -
130 - 17.8 15.3 12.6
135 - - 16.5 13.5
140 - - 17.5 14.5
145 - - - 16.5
(Unit: CMM)
(Unit: CMM)
Setting Value
Static Pressure[mmAq(Pa)]
4(49) 6(59) 8(78) 10(98)
100 20.8 - - -
105 23.2 19.5 - -
110 26.0 21.5 - -
115 - 23.5 19.1 -
120 - 26.3 21.6 -
125 - - 24.0 19.9
130 - - 27.0 22.7
135 - - - 25.9
(Unit: CMM)
Models : ABNQ18GHLA0, ABNQ21GHLA0
Models :
ABNQ24GGLA0
Models :
ABNQ36GGLA0
Setting Value
Static Pressure[mmAq(Pa)]
6(59) 8(78) 10(98) 12(118) 14(137)
80 14.8 - - - -
90 19.0 14.4 - - -
100 23.3 19.7 13.9 - -
110 26.9 24.3 19.8 14.1 -
120 31.2 28.2 25.2 20.1 14.4
130 34.9 32.4 29.5 25.4 20.5