Part 2 Functions & Controls
Table 2
Model Mode Set value
Standard ESP
(mmAq(Pa))
CMM
Lower Limit of
External Static
Pressure
(mmAq(Pa))
Upper Limit of
External Static
Pressure
(mmAq(Pa))
ABNQ18GHLA0
Hi
8 (78)
16.5
2.5(25) 8 (78)Mid 14.5
Low 13.0
ABNQ21GHLA0
Hi
8 (78)
16.5
2.5(25) 8 (78)Mid 14.5
Low 13.0
ABNQ24GGLA0
Hi
8 (78)
16.5
2.5(25) 8 (78)Mid 14.5
Low 13.0
ABNQ36GGLA0
Hi
10 (98)
32.0
4.0(39) 10 (98)Mid 29.0
Low 26.0
ABNQ42GRLA0
Hi
10 (98)
28.0
5.0(49) 10 (98)Mid 26.0
Low 32.0
ABNQ48GRLA0
Hi
10 (98)
40.0
5.0(49) 10 (98)Mid 35.0
Low 30.0
ABNQ54GRLA0
Hi
10 (98)
50.0
5.0(49) 10 (98)Mid 45.0
Low 40.0
1450
1400
1340
1450
1400
1340
1270
1210
1090
1370
1310
1260
1060
1020
990
1100
1060
1030
1240
1200
1150
[Notes]
1. To get the desired Airflow & E.S.P. combination from the table set the matching value from the table. Value other than
that in table will not give the combinations of airflow & E.S.P. which are mentioned in the table.
2. Table data is based at 230V. According to the fluctuation of voltage, air flow rate varies.
Static pressure(mmAq) 0 1 2 3 4
Model Step(Hi/Mid/Low) Setting value
ABNQ18GL2A0
15 CMM 90 97 105 114 122
12.5 CMM 82 90 99 109 119
10 CMM 75 84 93 103 114
ABNQ21GL2A0
17.5 CMM 90 97 105 114 122
14 CMM 82 90 99 109 119
12 CMM 75 84 93 103 114
ABNQ24GL3A0
20 CMM 110 117 125 129 -
16 CMM 100 107 115 121 127
12 CMM 90 97 105 114 122