46
[Table. 1]
Note: 1. Be sure to set the value refering table 1. Unexpected set value will cause mal-function.
2. Table 1 is based at 230V. According to the fluctuation of voltage, air flow rate varies.
Optional Operation
1. Air conditioners should not be installed in areas where corrosive gases, such as acid or alkaline
gas, are produced.
2. Do not install the product where it could be exposed to sea wind (salty wind) directly. It can result
corrosion on the product. Corrosion, particularly on the condenser and evaporator fins, could cause
product malfunc-tion or inefficient performance.
3. If outdoor unit is installed close to the seaside, it should avoid direct exposure to the sea wind.
Otherwise it needs additional anticorrosion treatment on the heat exchanger.
Selecting the location(Outdoor Unit)
1) If the outdoor unit is to be installed close to the seaside, direct exposure to the sea wind should be
avoided. Install the outdoor unit on the opposite side of the sea wind direction.
2) In case, to install the outdoor unit on the seaside, set up a windbreak not to be exposed to the sea wind.
3) Place with fluent water draining
Install at a place with fluent water draining to prevent damage from localized heavy rain and avoid
frequent flooded area.
1. If you can’t meet above guide line in the seaside installation, please contact LG Electronics for the
additional anticorrosion treatment.
2. Periodic (more than once/year) cleaning of the dust or salt particles stuck on the heat exchanger by
using water
• It should be strong enough like concrete to
prevent the sea wind from the sea.
• The height and width should be more than
150% of the outdoor unit.
• It should be keep more than 70 cm of space
between outdoor unit and the windbreak for
easy air flow.
Sea wind Sea wind
Sea wind
Windbreak
Installation guide at the seaside
Static Pressure(mmAq) 0 2 4 6 8
Model Name Step CMM(CFM) Setting Value
ABNH186HLAD
[UB18 NHD]
High 16.5(583) 235 230 225 215 180
Med 14.5(512) 245 238 235 230 215
Low 13(459) 254 252 248 245 240