Part 4 Trouble Shooting
Cause of
Trouble
Condition Mechanism of Fault Generation
Generation
of refrigerant
flow distur-
bance
Bending/Blocking of a pipe
EEV fault Closing of SVC Valve
Freezing of indoor device
→ Reduced evaporation temperature due to
excessive expansion of refrigerant.
Weak heating and cooling
→ Insufficient flow of refrigerant
Frequent turning on/off of the compressor by
the high/low pressure protection logic
→ Accumulated refrigerant elevates the tem-
perature and reduces the pressure.
Wrong oil collection elevates the outlet tem-
perature of the compressor and damages the
compressor.
■ Bending/Blocking of a pipe ■ Checking SVC Valve
Bending of a pipe
Check pipes
SVC Valve
Check
EEV Check
Replacing a part of or
the entire pipes
SVC Valve Full Open
Replacing EEV
※ EEV Checking Method :
Check the opening/closing
sound of EEV when the power
is applied for the first time.
Generation of refrigerant flow disturbance
6.6 Troubleshooting Outdoor Error
CH 21 (DC Peak / Comp IGBTM Fault)