EasyManua.ls Logo

LG LB-H2460FH - Refrigeration Cycle Diagrams; Heat Pump Cycle

LG LB-H2460FH
71 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Refrigeration Cycle Diagram
HEAT PUMP (LB-H1860RH/LB-H2460RH/LB-G3680RH/LB-G3660RH/
LB-G3660PH/LB-E4880RH/LB-E6080RH)
13
INDOOR UNIT OUTDOOR UNIT
HEAT
EXCHANGER
HEAT
EXCHANGER
COMPRESSOR
GAS SIDE
LIQUID SIDE
COOLING
HEATING
REVERSING
VALVE
CAPILLARY TUBE
Rated performance for refrigerant line length of: 7.5m
If 18K Model is installed at a distance of 15m, 255g of refrigerant should be added (15-7.5)x30g=225g
LB-H1860RH 5/8" 1/4" 7.5 50 5 30 30
LB-H2460RH 5/8" 1/4" 7.5 50 5 30 30
LB-G3660RH/PH 5/8" 1/4" 7.5 50 5 30 40
LB-G3680RH 5/8" 1/4" 7.5 50 5 30 40
LB-E4880RH 3/4" 3/8" 7.5 50 5 30 40
LB-E6080RH 3/4" 1/2" 7.5 50 5 30 80
Pipe size(Diameter: ø) Piping length(m) Elevation(m)
MODEL
Gas Liquid Rated Max. Rated Max.
*Additional
refrigerant
(g/m)

Related product manuals