• Rated performance for refrigerant line length of: .7.5m
• If 18K Model is installed at a distance of 15m, 225g of refrigerant should be added (15-7.5)x30g=225g
LB-H1860FH 5/8" 1/4" 7.5 50 5 30 30
LB-H2460FH 5/8" 1/4" 7.5 50 5 30 30
LB-G3660FH 5/8" 1/4" 7.5 50 5 30 40
LB-G3680FH 5/8" 1/4" 7.5 50 5 30 40
LB-E4880FH 3/4" 3/8" 7.5 50 5 30 40
LB-E6080FH 3/4" 1/2" 7.5 50 5 30 80
*Additional
refrigerant
(g/m)
Pipe size(Diameter: ø) Piping length(m) Elevation(m)
MODEL
Gas Liquid Rated Max. Rated Max.