EasyManua.ls Logo

LG LB-H2460RH - Installation Procedures

LG LB-H2460RH
71 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
24
Installation of Indoor, Outdoor Unit
1. Selection of the best location
1) Indoor unit
Select location
Install the air conditioner in the location that satis-
fies the following conditions.
The place shall easily bear a load exceeding four
times the indoor units weight.
The place shall be able to inspect the unit as the
figure.
The place where the unit shall be leveled.
The place shall allow easy water drainage.(Suit-
able dimension H is necessary to get a slope to
drain as figure.)
The place shall easily connect with the outdoor
unit.
The place where the unit is not affected by an
electrical noise.
The place where air circulation in the room will be
good .
There should not be any heat source or steam
near the unit
2) Outdoor unit
If an awning is built over the unit to prevent direct
sunlight or rain exposure, be careful that heat
radiation from the condenser is not restricted.
There should not be any animals or plants which
could be affected by hot air discharged.
Ensure the spaces indicated by arrows from the
wall, ceiling, fence or other obstacles.
3) Piping length and the elevation
Indoor unit
Outdoor unit
B
A
More than
30cm
More than
30cm
More than
70cm
Sunroof
Fence or
obstacles
H
600600
Top view
(unit: mm)
Front view
Front
Inspection hole
(600X600)
Control box
1000
If 18K Model is installed at a distance of 15m, 225g of
refrigerant should be added (15-7.5) x 30g = 225g
Capacity is based on standard length and maximun
allowance length is on the basis of reliability.
Improper refrigerant charge may result in abnormal
cycle.
18K/24K BTU/h
36K BTU/h
48K BTU/h
60K BTU/h
30
40
40
80
Capacity
Gas
5/8"
5/8"
3/4"
3/4"
Liquid
1/4"
1/4"
3/8"
1/2"
Elevation B(m)
Length A(m)
*Additional
refrigerant
(g/m)
Pipe Size
(Diameter: Ø)
Standard
7.5
7.5
7.5
7.5
Standard
5
5
5
5
Max.
50
50
50
50
Max.
30
30
30
30

Related product manuals