10 Ceiling Duct Type Air Conditioner
Installation of Indoor, Outdoor Unit
Piping length and the elevation
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
A
Oil trap
Outdoor unit
Indoor unit
B
If piping length is more than 5m
85
Capacity
Gas
3/4"
Liquid
1/2"
Elevation B(m)
Length A(m)
*Additional
refrigerant
(g/m)
Pipe Size
(Diameter: Ø)
Standard
7.5
Standard
5
Max.
50
Max.
30
60k Btu/h(3ø)
CAUTION:
If 60k Model is installed at a distance of 50m, 3612.5g of refrigerant
should be added (50-7.5) x 85g = 3612.5g
Capacity is based on standard length and maximun allowance length
is on the basis of reliability.
Improper refrigerant charge may result in abnormal cycle.
Oil trap should be installed every 10 meters.