10 Ceiling Duct Type Air Conditioner
Installation of Indoor, Outdoor Unit
Piping length and the elevation
CAUTION:
• If 60k Model is installed at a distance of 50m, 3612.5g of refrigerant
should be added (50-7.5) x 85g = 3612.5g
• Capacity is based on standard length and maximun allowance length
is on the basis of reliability.
• Improper refrigerant charge may result in abnormal cycle.
• Oil trap should be installed every 10 meters.