Installation Manual 9
ENGLISH
Installation of Indoor, Outdoor Unit
Installation of Indoor, Outdoor Unit
Indoor unit
Install the air conditioner in the location that
satisfies the following conditions.
The place shall easily bear a load exceeding
four times the indoor units weight.
The place shall be able to inspect the unit as
the figure.
The place where the unit shall be leveled.
The place shall allow easy water
drainage.(Suitable dimension H is necessary
to get a slope to drain as figure.)
The place shall easily connect with the outdoor
unit.
The place where the unit is not affected by an
electrical noise.
The place where air circulation in the room will
be good .
There should not be any heat source or steam
near the unit
Outdoor unit
If an awning is built over the unit to prevent
direct sunlight or rain exposure, be careful that
heat radiation from the condenser is not
restricted.
There should not be any animals or plants
which could be affected by hot air discharged.
Ensure the spaces indicated by arrows from
the wall, ceiling, fence or other obstacles.
Selection of the best location
H
600600
Top view
(unit: mm)
Front view
Front
Inspection hole
(600X600)
Control box
1000
More than
30cm
More than
30cm
More than
70cm
Sunroof
Fence or
obstacles