■ Tighten the flare nut with a wrench.
■ When extending the drain hose at the indoor unit, install
the drain pipe.
6. Wrap the insulation material around the connecting
portion.
■ Overlap the connection pipe insulation material and the
indoor unit pipe insulation material. Bind them together
with vinyl tape so that there is no gap.
■ Wrap the area which accommodates the rear piping hous-
ing section with vinyl tape.
■ Bundle the piping and drain hose together by wrapping
them with vinyl tape over the range within which they fit
into the rear piping housing section.
1. Route the indoor tubing and the drain hose to the
required piping hole position.
2. Insert the piping, drain hose and the connecting
cable into the piping hole.
- 28 -
Pipe Size[Torque]
GAS LIQUID
9K 1/2"[5.5kg.m] 1/4"[1.8kg.m]
12K 1/2"[5.5kg.m] 1/4"[1.8kg.m]
18K 5/8"[6.6kg.m] 1/4"[1.8kg.m]
24K 5/8"[6.6kg.m] 3/8"[4.2kg.m]
Capacity
(Btu/h)
For right rear piping