12 | PRODUCT DATA
Single Zone Wall Mounted Extended Piping Engineering Manual
Due to our policy of continuous product innovation, some specications may change without notication.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG ” is a registered trademark of LG Corp.
ELECTRICAL DATA
Model Number Nominal Tons Compressor Qty
Compressor (A)
Cool / Heat
Fan Qty
Outdoor Unit
Fan (A)
MCA (A) MOP (A)
LS243HLV
2 1 14.6/14.6 1 0.25 19 30
LS303HLV
2-1/2 1 14.6/14.6 1 0.25 19 30
LS363HLV
2-3/4 1 14.6/14.6 1 0.25 19 30
Table 3: Single Zone Wall Mounted Extended Piping Electrical Data
Voltage tolerance is ±10%.
Maximum allowable voltage unbalance is 2%.
RLA = Rated Load Amps.
MCA = Minimum Circuit Ampacity.
Maximum Overcurrent Protection (MOP) is calculated as follows:
(Largest motor FLA x 2.25) + (Sum of other motor FLA) rounded down
to the nearest standard fuse size.
Recommended fuse size: 25A.