Part 5. Trouble Shooting
- 73 -
Copyright ©2017 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Display
code
Title Cause of error Check point & Normal condition
32
High temperature in Dis-
charge pipe of the inverter
compressor
• Overload operation (Out-
door fan constraint,
screened, blocked)
• Refrigerant leakage (in-
sufficient)
• Poor INV Comp Dis-
charge sensor
• LEV connector displaced
/ poor LEV assembly
• Check outdoor fan constraint/ screened/ flow
structure
• Check refrigerant leakage
• Check if the sensor is normal
• Check the status of EEV assembly
CN- DISCHARGE
(BLACK 3Pin Connector)
Replace the Thermistor
Yes
CN_TH3
(RED 4Pin Connector)
WARNING
Before checking PCB or each outdoor electric parts, wait for 3 minutes after the power is off. When measuring at standby state
of power supply, after checking the measurement mode of the meter, be careful of the short-circuits with other parts.

Table of Contents

Other manuals for LG LSN HSV4 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LG LSN HSV4 Series and is the answer not in the manual?

LG LSN HSV4 Series Specifications

General IconGeneral
BrandLG
ModelLSN HSV4 Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals