Electrical
Table 3: Vertical Air Handling Unit ODU Electrical Data.
Electrical Data
Voltage tolerance is ±10%.
Maximum allowable voltage unbalance is 2%.
RLA = Rated Load Amps.
MCA = Minimum Circuit Ampacity.
Maximum Overcurrent Protection (MOP) is calculated as follows:
(Largest motor FLA x 2.25) + (Sum of other motor FLA) rounded
down to the nearest standard fuse size.
Nominal
Tons
Model
Name
Unit Power Supply Compressor
Quantity
Compres-
sor
Motor RLA
(Cooling)
Condenser Fan Motor(s)
Hz Volts Voltage
Range
MCA MOP Condens-
er
Fan
Quantity.
Condenser
Fan
Motor FLA
1.0 LVU120HCV
60 208/230
Min.: 187
Max.: 253
13.8 20 1 10.0 1 1.3
1.5 LVU180HCV 15.4 25 1 11.3 1 1.3
2.0 LVU240HCV 16.6 25 1 12.2 1 1.3
2.5 LVU300HCV 19.5 30 1 14.3 1 1.6
GENERAL DATA