INSTALLATION
,QVWDOO&DVVHWWH)UDPH
Figure 11: Paper Template or Corrugated Cardboard Used as a Guide
(Example Only; Appearances Will Vary Depending on Model).
Figure 12: Accessing the Paper Template or Corrugated Cardboard
Used as a Guide (Example Only; Appearances Will Vary Depending on
Model).
16-1/8 Hanging Bolt
23-5/8
25-1/4 Ceiling Opening
(Unit: Inch)
40-11/16 Ceiling Opening
33-11/16 Hanging Bolt
32-11/16
2-3/8
116(4-9/16)4-9/16
Preparing the Installation Area Using
the Cassette Template
1. Cassette indoor units include installation guides (templates) that
depict the exact dimensions necessary for the ceiling opening.
One is a paper template that is found in the cassette indoor unit
shipping materials; the other template is the cardboard on the
bottom of the packaging.
2. Use the provided paper template or corrugated cardboard from
the bottom packaging as a guide to determine the size of the ceil-
ing opening and the hanging bolt locations required by the unit.
The dimensions of the paper model for installation are the same
as those of the ceiling opening dimensions. To access, carefully
cut away corrugated cardboard from the packing material.
3. Using one of the templates, choose the location for the indoor
unit. Mark where the four (4) suspension / hanger bolts, refriger-
ant piping, and drain hose should be. Suspension bolt angle must
account for drain direction.
Paper Template
or
Corrugated Cardboard
From the Bottom Packaging
Figure 13: Ceiling Opening / Hanging Bolt Locations for One-Way
Ceiling Cassette Indoor Units.
Figure 14: Ceiling Opening / Hanging Bolt Locations for Two-Way Ceiling
Cassette Indoor Units.
Unit: Inch
TT Frame
TU Frame
50-19/32 (Hanging Bolt)
54-17/32 (Ceiling Opening)
1-31/32
9-27/32
23-5/8
46-29/64
17-41/64
23-5/8
9-27/32
37-63/64 (Hanging Bolt)
41-59/64 (Ceiling Opening)
33-55/64
17-41/64
12-3/64
15-3/4 1-37/64
1-37/64
15-3/4 1-37/641-37/64
12-3/64
13-15/16
(Hanging Bolt)
18-11/32
(Ceiling Opening)
18-11/32
(Ceiling .Opening)
1-31/32
1-31/32
1-31/32
13-15/16
(Hanging Bolt)