EasyManua.ls Logo

LG MULTI V IV PRO ARUV100LLS4 - Page 87

LG MULTI V IV PRO ARUV100LLS4
91 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ELECTRICAL WIRING
87
ENGLISH
Display Title Cause of Error
Outdoor unit related error
1 8 2
1
Master outdoor unit External Board
Main-Sub Micom communication Error
Master Outdoor Unit Main Board Main-Sub Micom
communication failed
2
Slave1 outdoor unit External Board
Main-Sub Micom communication Error
Slave1 Outdoor Unit Main Board Main-Sub Micom
communication failed
3
Slave2 outdoor unit External Board
Main-Sub Micom communication Error
Slave2 Outdoor Unit Main Board Main-Sub Micom
communication failed
4
Slave3 outdoor unit External Board
Main-Sub Micom communication Error
Slave3 Outdoor Unit Main Board Main-Sub Micom
communication failed
1 9 3
1
Master Outdoor Unit Fan Heatsink High
Temperature
System is turned off by Master Outdoor Unit Fan
Heatsink High Temperature
2
Slave1 Outdoor Unit Fan Heatsink High
Temperature
System is turned off by Slave1 Outdoor Unit Fan
Heatsink High Temperature
3
Slave2 Outdoor Unit Fan Heatsink High
Temperature
System is turned off by Slave2 Outdoor Unit Fan
Heatsink High Temperature
4
Slave3 Outdoor Unit Fan Heatsink High
Temperature
System is turned off by Slave3 Outdoor Unit Fan
Heatsink High Temperature
1 9 4
1
Master Outdoor Unit Fan Heatsink
Temperature Sensor Fault
Master Outdoor Unit Fan Heatsink Temperature Sen-
sor open or short
2
Slave1 Outdoor Unit Fan Heatsink Tem-
perature Sensor Fault
Slave1 Outdoor Unit Fan Heatsink Temperature Sen-
sor open or short
3
Slave2 Outdoor Unit Fan Heatsink Tem-
perature Sensor Fault
Slave2 Outdoor Unit Fan Heatsink Temperature Sen-
sor open or short
4
Slave3 Outdoor Unit Fan Heatsink Tem-
perature Sensor Fault
Slave3 Outdoor Unit Fan Heatsink Temperature Sen-
sor open or short

Related product manuals