EasyManua.ls Logo

LG MULTI V S ARUV060GSD0 - Page 35

LG MULTI V S ARUV060GSD0
69 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT
35
ENGLISH
Refrigerant pipe diameter from branch to branch (B,C)
Downward Indoor Unit
total capacity [kW(Btu/h)]
Liquid pipe [mm(inch)] Gas pipe [mm(inch)]
5.6(19,100)
Ø6.35(1/4) Ø12.7(1/2)
< 16.0(54,600) Ø9.52(3/8) Ø15.88(5/8)
22.4(76,400)
Ø9.52(3/8) Ø19.05(3/4)
< 36.4(124,200) Ø9.52(3/8) Ø22.2(7/8)
Refrigerant pipe diameter from outdoor unit to first branch. (A)
Outdoor unit
total capacity (HP)
Liquid pipe [mm(inch)] Gas pipe [mm(inch)]
2.5 Ø9.52(3/8) Ø15.88(5/8)
3 Ø9.52(3/8) Ø15.88(5/8)
4 Ø9.52(3/8) Ø15.88(5/8)
5 Ø9.52(3/8) Ø15.88(5/8)
6 Ø9.52(3/8) Ø19.05(3/4)

Related product manuals