Product Data
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
LG Headers serve as central connections for multiple runout pipe segments
terminating at indoor units.
Headers must be used with LG systems and be properly installed following the
instructions in the applicable LG manual. Field-supplied headers are not permitted.
Kit components must be kept dry and free of debris before installation.
All Header Kits include:
- Insulation jacket (one each for vapor and liquid pipes)
- Plugging tubes / Insulation for plugging tubes (see Table 34).
Model Fitting Capacity Port Capacity
ARBL054 (4 branch)
≤72,000 connected capacity ≤54,300 per port
ARBL057 (7 branch)
≤75,100 connected capacity ≤54,300 per port
ARBL1010 (10 branch)
≤172,200 connected capacity ≤76,300 per port
ARBL104 (4 branch)
≤305,200 connected capacity ≤76,300 per port
ARBL107 (7 branch)
≤534,000 connected capacity <76,300 per port
ARBL2010 (10 branch)
≤560,000 connected capacity ≤76,300 per port
Table 33: Nominal Capacity Range.
Header Kits
Table 34: Plugging Tubes and Plugging Tube Insulation Amounts.
Header Kits
Plugging Tubes (in OD)
Insulation for Plugging Tubes
1/4 1/2 5/8
ARBL054 (4 port)
ARBL057 (7 port) 2 2 4
ARBL1010 (10 port) 2 2 2 6
ARBL104 (4 port)
ARBL107 (7 port) 2 2 2 6
ARBL2010 (10 port) 2 2 2 6
Table 35: Insulation Jacket Properties.
Material
Polyolefin Foam
UL94 Flame Classication
HF-1
Density
1.84 lbs./ft.
3
Thermal Conductivity
.0208 Btu/h/ft. ºF
Thickness
1/2 inch
Material
Copper
Design Pressure
550 psig
Table 36: Fitting Properties.
CUT SHEETS