LG MW242H4 - CHARGING THE REFRIGERANT; Charge Using the Refrigerant Cylinder without a Siphon

LG MW242H4
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
17
EN
CHARGING THE REFRIGERANT
If the amount of refrigerant level is low, the appliance
would provide low performance. Charge the
refrigerant for proper operation.
Refer to the label attached to the side of the
appliance to confirm the type and amount of
refrigerant.
Charge the refrigerant through the gas service
valve (larger pipe).
1
Connect the low-pressure hose of the manifold
gauge to the core valve of the gas service valve.
Lo Hi
2
Open both the gas service valve and the liquid
service valve of the outdoor unit.
Rotate the valves to counter-clockwise using a
hexagon wrench.
3
Connect the charging hose of the manifold
gauge to the refrigerant cylinder.
Charge Using the Refrigerant Cylinder
without a Siphon
This is usually applied to R410A. Charge
the refrigerant (liquid phase) by inverting the
refrigerant cylinder.
Lo Hi
4
Charge the refrigerant by adjusting the low-
pressure valve of the manifold gauge.
Refer to ‘Suggested Amount of Refrigerant
Charge’.
5
After charging the refrigerant, close the low-
pressure valve of the manifold gauge and
separate the connected low-pressure hose from
the outdoor unit.
NOTE
If charging a mixed refrigerant like R410A, charge
from the bottom after removing all the refrigerant
in the cylinder.
The handling of the refrigerant must comply with
national regulations.

Table of Contents