18
PAHCMR000 AHU Communication Kit Installation Manual
Due to our policy of continuous product innovation, some specications may change without notication.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
L
HI
MED
LO W
AHU Communication Kit
H EX
Motor Control (MCC) Panel
M
N
Air Handler Unit
Motor Input Power
1Ø, 208/230 V ~ 60 Hz
M
Motor
Relay
Field Wiring
Factory Wiring
L1 L2
Control Power
1Ø, 208/230 V ~ 60 Hz
Cable : Over CV 15AWG
220-240 V ~ 50/60 Hz
R-LOWR-MED
R-HI
LOW (L)
MED (L)
HI (L)
DO1 DO2 DO3
L1(L) L2(N)
AHU Communications Kit to Air Handler Unit Connection (Fan Motor Control)
AHU COMMUNICATIONS KIT INSTALLATION
• AHU manufacturer-supplied relays must be used
to connect the LG AHU Communications Kit to the
AHU fan motor.
• MCC panel means motor control panel.
Connection for Fan Signal
Figure 9: AHU Communications Kit to AHU Connection (For Fan Signal).
AHU Communications Kit Hi/Med/Low wires should
not be connected directly to the AHU fan motor�
Improper connections could result in re, electric
shock, physical injury or death�
• AHU Communications Kit Hi/Med/Low
wires should not be connected directly
to the AHU fan motor� Improper connec-
tions could result in product damage�
• If the third-party AHU fan motor is the On/Off
type, the HI/MED/LOW wires from the motor
control panel to the AHU have to connect as
one common wire� Example: If just the Hi wire is
connected, the fan motor will not operate using
the LG AHU Communications Kit control logic�