Control Functions
AHU COMMUNICATIONS KIT INSTALLATION
BMS Protocol - PAHCMR000 Modbus Points
Modbus Points - Function Codes
Notes:
Register Description
0: Normal / 1: Oil Return
0: Cooling / 2: Fan / 4: Heating
1: Low / 2: Middle / 3: High
15.6 ~ 30°C (×10, 1.0°C )
Write Single Holding Register
1. Configuration is 9600bps, parity none, and stop bit 1.
2. To change slave address, refer to main module address setting.
15.6 ~ 30°C
Modbus Points - Memory Map