Specifications
Table 9: EEV Kit Specications Table.
Figure 16: EEV Kit.
Introduction
When used with the LG AHU Communications Kit (sold separately), the LG EEV Kit controls refrigerant flow between
LG Multi V air-source or water-source units and a third-party air handler unit (AHU).
The EEV Kits for PAHCMR000 are offered in three sizes:
• PRLK048A0 supports 12 through 96 MBH (8 tons maximum)
• PRLK096A0 supports 96.1 through 192 MBH (16 tons maximum)
• PRLK396A0 supports 192.1 MBH through 396 MBH (32 ton maximum)
EEV KIT INSTALLATION
Introduction, Specications, and Design Parameters
Table 10: EEV Kit Compatibility Table.
EEV Kit Design Parameters
• Maximum of one (1) EEV Kit can be connected to one (1) AHU
Communications Kit.
• Minimum coil entering air temperature for heating mode is 41°F.
• Requires field-supplied six-conductor communication cable to
connect to AHU Communications Kit.
• Maximum distance between EEV Kit and AHU Communications Kit
is thirty-two (32) feet.
• Designed for indoor installations (field-supplied waterproof enclo-
sure must be used when installing outdoors).
PRLK048A0
(8 tons max)
HP/HR HP
(16 tons max)
HP HP
(32 tons max)
HP HP
PRLK594A0
(48 tons max)
NA
HP (requires EEV
module)
AHU Communica�on Kit
EEV Kit
HP = Heat Pump; HR = Heat Recovery
PRLK396A0
For Use With PAHCMR000 and PAHCMS000
Power Supply Requirements
Powered by Air Handler Unit Comm Kit (12 VDC)
Ambient Opera�ng
Temperature Range
- 4 to 149F
Ambient Opera�ng
Humidity Range
0 to 98% (Non-condensing)
Dimensions (in., W x H x D) 8-5/8 x 15-15/16 x 3-5/16
13-25/32 x 7-3/32
x 13-39/64-
Maximum Air Handler Unit
Capacity (Btu/h)
96,000 192,000 396,000
AWG 18 x 6 Stranded, Shielded Copper Wire