96 Outdoor Unit
Function
2.3 Oil equalizing control
• Equalizing operation of Compressor's oil operates for 2minutes every 60 minutes.
2.4 Stopping operation
2.4.1 Stopping operation on cooling mode
2.4.2 Stopping operation on heating mode
Inv Compressor
Fan
Main LEV
4way valve
Subcooling LEV
0Hz
0Hz
170 PLS
On
35 PLS
OperationComponent
After 15 min from stop, off
Note
Hot gas bypass On After 15 min from stop, Off
Inv Compressor
Fan
Main LEV
4way valve
Subcooling LEV
0Hz
0Hz
170 PLS
Off
35 PLS
OperationComponent
Off
-
-
-
-
-
-
-
-
Note
Hot gas bypass On
After 15 min from stop, Off