10. Installation
42
Outdoor unit
When installing the unit in a place that is constantly exposed to a strong wind like a coast or on a high story of
a building, secure a normal fan operation by using a duct or a wind shield.
1. Install the unit so that its discharge port faces to the wall of the building.Keep a distance 300mm or more
between the unit and the wall surface.
2. Supposing the wind direction during the operation season of the air conditioner, install the unit so that the
discharge port is set at right angle to the wind direction.
10.3 Installation Space
10.3.1 Clearance around outdoor units
Ensure that the space around the back is
or more more than 300 mm on the
opposite to the PCB side and secure 600
mm space near the compressor and PCB
side of the air conditioner for service.
Install the unit so that its discharge port
faces to the wall of the building. Keep a
distance 500mm or more between the unit
and the wall surface.
Supposing the wind direction during the
operation season of the air conditioner,
install the unit so that the discharge port is
set at right angle to the wind direction.
300 mm or more
300 mm or more
300 mm
or more
Sunroof
Fence or
obstacles
600 mm or more
(Service space)
100 mm
100 mm
or more
or more
300 mm
or more
700 mm
or more
Outdoor unit is representative. Actual appearance of outdoor unit
may be different but clearances will stay the same.
Air inlet grille
500
Blown
air
Strong
wind
Strong
wind
Turn the air outlet side toward the build-
ing's wall, fence or windbreak screen.
Set the outlet side at a right angle
to the direction of the wind.
Outdoor unit is representative. Actual appearance of outdoor unit may be
different but clearances will stay the same.