4
THERMA V Split Type
DHW Tank Integrated Unit
3. Specifications
Technical Specifications
Indoor Unit Model Name AHNW16606B0 [HN1616T NB0]
Operation
Range
(Leaving
Water)
Cooling
(Min.~Max.)
For Fan Coil Unit °C 7 ~ 25
For under floor °C 7 ~ 25
Heating
(Min.~Max.)
For Fan Coil Unit /Radiator °C 25 ~ 58
For under floor °C 25 ~ 58
Domestic Hot Water (Min.~Max.) °C 10 ~ 60
Operation Range (Ambient) °C 5 ~ 35
DHW Tank
Type Hydro module with integrated boiler
Material - Enameled steel
Water Volume Rated
˜
200
Internal Thermal Protect limit °C 95
Maximum water temperature °C 52
Maximum water pressure limit bar 10
Insulation
Material - Polyurethane foam
Thickness mm 50
Heat loss (for 24hr) kWh 1.67
Buffer Tank
Water Volume Rated
˜
40
Material - Steel powder coated
Insulation Material - Closed cell foamed rubber
Water Pump
Type - Canned type for hot water circulation
Model - Yonos PARA RS25/7 PWM1
Motor type - BLDC
Steps of Speed EA Variable speed 13% to 100%
Power input W 3 ~ 45
Water Flow Rate
Min.
˜ / min
16.0
Rated
˜ / min
46.0
Pressure drop Max. kPa 70
Heat
Exchanger
(Water Side)
Type - Brazed Plate HEX
Quantity - 1
Water Volume
˜
3.3
Water Flow Rate (Min. ~ Max.)
˜ / min
13 ~ 70
Insulation Material - Closed cell foamed rubber
Safety Valve Pressure Limit Max. bar 3
Devices for Water Circuit
- Manometer
- Drain Valve / Fill Valve
- Shut Off Valve
- Air Vent
Piping
Connections
Refrigerant
Circuit
Gas (Outer Dia.) mm(inch) Ø 15.88 (5/8)
Liquid (Outer Dia.) mm(inch) Ø 9.52 (3/8)
Water
Circuit
Inlet (Inner Dia.) mm(inch) Male PT 25 (1)
Outlet (Inner Dia.) mm(inch) Male PT 25 (1)
DHW Tank
Water
Circuit
Cold Inlet (Outer Dia.) mm(inch) Male PT 19.05 (3/4)
Hot Outlet (Outer Dia.) mm(inch) Male PT 25 (1)
Recirculation (Outer Dia.) mm(inch) Male PT 19.05 (3/4)
Sound Pressure Level dB(A) 27
Sound Power Level dB(A) 36
Dimensions (W × H × D)
Unit mm 607 × 2,079 × 725
Shipping mm 640 × 2,195 × 790
Weight
(without water)
Unit kg 228
Shipping kg 238
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national code. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound Level Values are measured at Anechoic chamber. Therefore, these values depend on the ambient conditions and values are normally higher
in actual operation.
4. Capacities are net capacities and based on the following conditions. Refer to the Outdoor Unit Specifications for calculating the real capacity.
Cooling : Indoor Water Temp. 23°C / 18°C, Outdoor Ambient Temp. 35°CDB / 24°CWB
Heating : Indoor Water Temp. 30°C / 35°C, Outdoor Ambient Temp. 7°CDB / 6°CWB
Interconnected Pipe is standard length and difference of Elevation (Outdoor ~ Indoor Unit) is Zero.
5. Sound pressure levels at a distance of 1m.
6. This is true for pipe connections of suitable dimensions and joint distance of up to 20m.
Pipe dimensions and types of pumps must always be verified or determined by the designing engineer of electrical installations.
Circulation pumps must be dimensioned in such a way so as to ensure rated voltage (see table) through the device.