E.S.P. setting value (reference)
Table 1
NOTE
1. Be sure to set the value refering table 1. Unexpected set value will cause mal-function.
2. Table 1 is based at 230V. According to the fluctuation of voltage, air flow rate varies.
3. Factory Set(External Static Pressure) each Model
* If it is zero static pressure, please set value below Maximum value.
Model Step CMM
Static Pressure[mmAq(Pa)]
Setting Value
ABNW85GB9A0
[UB85 N94]
LOW 64
MID 72
HIGH 80
Model Maximum value
ABNW85GB9A0
[UB85 N94]
ABNW70GB9A0
[UB70.N94]
105
Model Factory set (E.S.P.) mmAq(Pa)
ABNW85GB9A0
[UB85 N94]
ABNW70GB9A0
[UB70.N94]
13 (127)
6(59) 7(69) 8(78) 9(88) 10(98) 12(118) 13(127) 14(137) 15(147) 16(157) 18(176)
32:01 32:02 32:03 32:04 32:05 32:06 32:07 32:08 32:09 32:10 32:11
74 75 76 78 79 82 84 86 89 91 95
78 79 80 82 83 87 89 91 94 96 100
82 84 86 88 90 93 95 97 100 101 105
Model Step CMM
Static Pressure[mmAq(Pa)]
Setting Value
ABNW70GB9A0
[UB70 N94]
LOW 60
MID 65
HIGH 70
6(59) 7(69) 8(78) 9(88) 10(98) 12(118) 13(127) 14(137) 15(147) 16(157) 18(176)
32:01 32:02 32:03 32:04 32:05 32:06 32:07 32:08 32:09 32:10 32:11
70 72 74 76 78 81 82 85 86 88 91
74 76 78 80 82 85 86 89 90 92 95
78 80 82 84 86 90 91 93 94 96 99