Part 4 Trouble Shooting
- 41 -
Copyright ©2014 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
6.5 Troubleshooting Indoor Error
CH 01 (Indoor unit air sensor error
CH 02 (Indoor unit pipe inlet sensor error
CH 06 (Indoor unit pipe outlet sensor error)
01 Indoor unit air sensor error
02 Indoor unit pipe intake sensor error
06 Indoor unit pipe outlet sensor error
Error
No.
Error Type Error Point Main Reasons
Indoor unit sensor is
open/short
1. Indoor unit PCB wrong connection
2. Indoor unit PCB failure
3. Sensor problem (main reason)
** In case the value is more than 100kΩ (open) or less than 100Ω (short), Error occurs
Refer: Resistance value maybe change according to temperature of temp sensor,
It shows according to criteria of current temperature(±5% margin) ➔ Normal
Air temp sensor: 10°C = 20.7kΩ : 25°C= 10kΩ : 50°C= 3.4kΩ
Pipe temp sensor: 10°C = 10kΩ : 25°C= 5kΩ : 50°C= 1.8kΩ
■ Error diagnosis and countermeasure flow chart