Product Specification Sheet page 2 11/02 (Rev. 0)
Power Wiring
The LT410 is rated for 24 VAC, 50/60 Hz and
0.10 amp.
Figure 1 24V from Liebert environmental units to LT410
Figure 2 24V from transformer to LT410
Wiring to Auxiliary Alarm Panels
The LT410 has two Form-C dry contact alarm out-
put contacts: orange wires (1) and yellow wires (2).
Each contact is rated for 24 VAC at 3 amp.
Figure 3 LT410 to Liebert environmental units
Figure 4 LT410 to Liebert contact monitor panel
Power Wiring
24V from Liebert Environmental Unit to LT460
Liebert Deluxe Sys/3,
Challenger, Himod or
MM2 (8 Ton)
TB1
T5
(24V)
G5
(Ground)
LT460
TB1
TB1-1
TB1-2
ions)
(24V)
(Ground)
From 24V
transformer*
Red
Red
Red wires
Liebert Mini-Mate2
(1 to 5 ton)
LT410
* Requires a 24V external transformer (there are
no designated terminal connections on the unit)
Liebert Deluxe Sys/3,
Challenger, Himod or
MM2 (8 Ton)
TB1
T5
(24V)
G5
(Ground)
LT460
TB1
TB1-1
TB1-2
Transformer
LT460
TB1
TB1-1
TB1-2
From 24V
transformer
24V from Transformer to LT460
Liebert MM2 (1 to 5 Ton) LT460
TB1
TB1-1
TB1-2