System and Control Options
24
Figure 16 shows the main options available from the System & Control menu.
Figure 16 Menu overview - System and Control menu
Opening Screen
LIQUI-TECT PANEL
DD-MON-YY HR:MM:SS
VERSION X.X.X
PRESS
=STATUS/SETUP
Main Menu
VIEW STATUS
> SYSTEM AND CONTROL
↑↓=NEXT
=SELECT
Login Screen
LOGIN
AAAA
↑↓=SELECT =NEXT/END
Setup System
>SETUP SYSTEM
RESET LATCHED ALARM
CLEAR ALARM HISTORY
CLEAR ZONE TREND
See
Section
6.2
SETUP ZN1 ZONE 1
SETUP ZN2 ZONE 2
SETUP ALARM OUTPUTS
SETUP REALARM DELAY
SETUP MAPMODE
SETUP SYSTEM INFO
Reset Latched Alarm
SETUP SYSTEM
>RESET LATCHED ALARM
CLEAR ALARM HISTORY
CLEAR ZONE TREND
See
Section
6.9
Reset Latched Alarms
RESET LEAK & FAULT
LATCHED ALARMS? Y
↑↓=Y/N =END
System & Control options
Clear Zone Trend
SETUP SYSTEM
RESET LATCHED ALARM
CLEAR ALARM HISTORY
>CLEAR ZONE TREND
See
Section
6.11
Clear Zone Trend
CLEAR ZONE TREND
ARE YOU SURE? Y
↑↓=Y/N =END
Clear Alarm History
SETUP SYSTEM
RESET LATCHED ALARM
>CLEAR ALARM HISTORY
CLEAR ZONE TREND
See
Section
6.10
Clear Alarm History
CLEAR ALARM HISTORY
ARE YOU SURE? Y
↑↓=Y/N =END
Setup Zone 1 Menu
SETUP ZN1 ZONE 1
CONNECTED: N
LABEL: ZONE 1
UNITS: FT
AUTO CALIBRATE
WATER DETECT:150 UA
CONTAMINATED:050 UA
See
Section
6.3
Setup Mapmode
SELECT ZONE TO MAP
>ZN1 ZONE 1
ZN2 ZONE 2
VIEW LAST MAP
See
Section
6.7
Mapping Options
MAPPING ZN1 ZONE 1
CURRENT: 0UA
DISTANCE: ----
ENTRIES:0 ESC=EXIT
Setup System options
Setup System Info
SETUP SYSTEM INFO
CHANGE PASSWORD
CHANGE DATE & TIME
FACTORY DEFAULTS
See
Section
6.8
Setup Zone 2 Menu
SETUP ZN2 ZONE 2
CONNECTED: N
LABEL: ZONE 2
UNITS: FT
AUTO CALIBRATE
WATER DETECT:150 UA
CONTAMINATED:050 UA
See
Section
6.4
Setup Alarm Outputs
SELECT LONGEST
CABLE CONNECTED
>0-500FT (0-152.4 M)
0-1000FT (0-304.8M)
0-1500FT (0-472.2M)
0-2000FT (0-609.6M)
0-2500FT (0-762.0M)
0-3000FT (0-914.4M)
0-4000FT(0-1219.2M)
0-5000FT(0-1524.0M)
See
Section
6.5
Normally Open / Closed
ARE LEAK & FAULT
RELAYS NORMAL OPEN
OR NORMAL CLOSED? NO
↑↓=NO/NC =END
Latched / Unlatched
IS LEAK & FAULT
ALARM LATCHED? Y
↑↓=Y/N =END
Change Password Change Date & Time Factory Defaults
CHANGE PASSWORD
AAAA
See
Section
6.8.1
CHANGE DATE & TIME
DAYLIGHT SVG TIME: Y
18
-MAY-02 10:56:30
See
Section
6.8.2
RESTORE ALL DEFAULTS
ARE YOU SURE? N
See
Section
6.8.3
Change Realarm Delay
CHANGE REALARM DELAY
5
MINUTES
↑↓=SELECT
=END
See
Section
6.6
Setup System Info options