Controllers MCE06ADV – MCE12ADV
- 9 -
4 INSTALLATION AND START UP
This section contains information instructions and warnings that the user must follow by its own security
and to ensure safe operation of the device.
WARNING! MCExxADV
regulators are usually connected to equipment containing
capacitors, which remain charged after removing supply voltage. To avoid risk of electric
shock, you must wait at least 5 minutes between the disconnection of the equipment
and handling of the internal components thereof.
Any handling or use of equipment in different way or conditions to that specified by
the manufacturer, may compromise the user safety.
In case that some damage or deterioration signs are detected in the device or a wrong operation is
observed, disconnect the supply voltage and contact INTERNATIONAL CAPACITORS,S.A. authorized
technical service.
To safely use the MCExxADV and MCExxADV it is important that people installing it or handling it follow
the usual safety precautions stated in the LV or MV Electrical Code Rules of each Country as well as the
different warnings stated in this instruction manual.
4.1 Technical Characteristics
The main technical characteristics of every particular MCExxADV and MCExxADV device are printed in
the rear label (see fig. 1.2) and are also summarized in the following table.
Supply
and measuring circuit
voltage (Terminals C-D)
480, 400, 230 o 110 VCA ; +15% -10% ; 45-65 Hz , (see label)
Connect preferably to phases L2-L3.
Supply
Cables
Cross Section 1,5mm
2
Supply circuit protection
By means of a 0,5 to 2A fuse (gl type)
Current measurement circuit.
(Terminals A-B)
External Current Transformer (CT). Current ratio In /5. To be placed
preferably in phase L1.
Cables
for the current
measurement circuit (CT
secondary side)
Minimum cross section : 2,5mm
2
. If cable length between regulator
and CT must exceed 25m, increase the cross section by 1mm
2
every
10m or use a CT with a higher primary rated current.
Current margin
0,1 to 5 A (maximum overload +20%)
Measurements precision
Voltage and Current: 1%; cosϕ : 2% ± 1 digit
cosϕ
ϕϕ
ϕ setting margin
0,85 ind. A 0,85 cap. Default setting: 1
Power Consumption
6 VA (all relays OFF) ; 9,5VA (12 relays ON)
Screen
1 line x 3 digits x 7segments + 20 icons
Output
:
Relay contacts
Working voltage: 250 VCA, Admissible current: 10 A, AC1.
Cabl
ing and protection of relays
output.
Minimum cables cross section: 1,5mm
2
, Protect by means of a
circuit breaker 6A, curve C or fuse 6A, gl type
Alarm relay
In case that not all the relay outputs are used to drive the capacitors,
the highest number relay is by default configured as alarm relay.
Reference standards
EN 61010, EN 61000-3-2, EN 61000-3-3, EN 50081-2, EN 50082-1,
EN 50082-2, EN 61000-4-2, EN 61000-4-4, EN 61000-4-8,
EN 61000-4-5, EN 61000-4-11 , UL 94
Safety and Insulation class
Installation Category III. Protection against electrical shock with
double insulation (class II ), according to EN 61010-1
Protection degree
IP51 (device mounted in panel front)
IP30 (device case) according to EN-60529
Environment admissible
conditions
Temperature: -20ºC a +60ºC; Relative humidity: max. 95% (without
condensation). Max. altitude: 2000m
Control system
FCP (Program which minimizes the number of operations)