10HP and below: 10s
15HP and 20HP: 15s
25HP and above: 20s
Min.: 0.1 s
Max.: 1000.0 s
Stop mode
selection upon
V/F separation
0 : Frequency and voltage
declining to 0 independently
1 : Frequency declining to 0 after
voltage declines to 0
Default: 0
Min.: 0
Max.: 1
Sets the motor rated current. This will be set
automatically during Auto-Tuning.
Default: o2-03, A1-06
Min.: 10% of drive
rated current
Max.: 200% of drive
rated current
Motor Rated
Speed (For Slip
Compesation)
Sets the motor rated speed used for slip
compesation. This will be set automatically
during Auto-Tuning. Alarm OPE17 will be
detected when this value is set incorrectly.
Default: o2-03, A1-06
Min.: 0 rpm
Max.: 60000 rpm
Sets the motor no-load current. This will be
set automatically during Auto-Tuning.
Default: o2-03, A1-06
Min.: 0.0 A
Max.: d2-00
(excluding d2-00)
Sets the number of motor poles. This will be
set automatically during Auto-Tuning.
Default: 4
Min.: 2
Max.: 48
Motor Line-to-
Line Resistance
Sets the line-to-line resistance. This will be set
automatically during Auto-Tuning.
Default: o2-03, A1-06
Min.: 0.000 Ω
Max.:65.000 Ω
Sets the voltage drop caused by the motor
leakage inductance relative to the motor rated
frequency and current. This will be set
automatically during Auto-Tuning.
Default: o2-03, A1-06
Min.: 0.00 mH
Max.:650.00 mH
Sets the motor rotor resistance. This will be
set automatically during Auto-Tuning.
Default: o2-03, A1-06
Min.: 0.000 Ω
Max.:65.000 Ω
Sets the motor mutual inductance. This will
be set automatically during Auto-Tuning.
Default: o2-03, A1-06
Min.: 0.0 mH
Max.:6500.0 mH
Sets the motor rated capacity. This will be set