101
Parameter
Name
Description
Setting Range
Capacity
automatically during Auto-Tuning. (1HP =
0.746 kW)
Min.: 0.00 kW
Max.: 650.00kW
Group E, Multi-Function Terminals
E1: Multi-Function Digital Inputs
E1-00
Terminal S1
Function
Selection
0 : 2-Wire Sequence Control (Forward/Stop) /
3-Wire Sequence Control (Stop)
1 : 2-Wire Sequence Control (Reverse/Stop) /
3-Wire Sequence Control (Stop)
2 : 3-Wire Sequence
3 : Local/Remote Selection
4 : Command Source 1/2 Selection
5 to 8: Multi-Step Speed Command 1 to 4
9 : Jog Frequency
10 : Up Command
11: Down Command
12: Up 2 Command
13: Down 2 Command
14, 15: FJOG/RJOG Command
16: Acc./Dec. Time Selection 1
17: Acc./Dec. Time Selection 2
18: Acc./Dec. Ramp Hold
19: Base Block
21: Fast Stop (Normal Open)
23 to 38 : External Fault
39: Fault Reset
40 : oH2 (AC drive Overheat Alarm)
41 : Multi-Function Analog Input Selection
45: Communication Mode
46: PID Disable
47: PID Integral Reset
48: PID Integral Hold
49: PID Soft-Start On/Off
50: PID Input Characteristics Switch
51: Motor 1/2 Switch
52: Timer Input
53, 54, 55: Offset Frequency 1/ 2/ 3
57: KEB Command 1 (Normal Open)
60: Program Lockout
61: Analog Frequency Command Hold
Default : 0
Min.: 0
Max.: 0 to 75 / 100 to
175
E1-01
Terminal S2
Function
Selection
Default : 1
Min.: 0
Max.: 0 to 75 / 100 to
175
E1-02
Terminal S3
Function
Selection
Default : 23
Min.: 0
Max.: 0 to 75 / 100 to
175
E1-03
Terminal S4
Function
Selection
Default : 39
Min.: 0
Max: 0 to 75 / 100 to
175
E1-04
Terminal S5
Function
Selection
Default : 5
Min.: 0
Max.: 0 to 75 / 100 to
175
E1-05
Terminal S6
Function
Selection
Default : 6
Min.: 0
Max.: 0 to 75 / 100 to
175
E1-06
Terminal S7
Function
Selection
Default : 9
Min.: 0
Range: 0 to 75 / 100
to 175