104
Parameter
Name
Description
Setting Range
Max.: 3600.0s
E2-08
Relay 2 On Delay
The definition of a relay2 on delay time.
Default: 0.0s
Min.: 0.0s
Max.: 3600.0s
E2-09
Relay 2 Off Delay
The definition of a relay2 off delay time.
Default: 0.0s
Min.: 0.0s
Max.: 3600.0s
E3: Multi-Function Analog Input
E3-00
Terminal A1
Signal Level
Selection
0 0 to 10 V
1 -10 to 10 V
Default: 0
Range: 0, 1
E3-01
Terminal A1
Function
Selection
0 : Main Frequency Command
1 : Frequency Gain
2 : Output Frequency Lower Limit
3 : Auxiliary Frequency Command
4 : Output Voltage Bias
5 : Acc./Dec. Time Gain (Decrease Only)
6 : DC Braking (DB) Current
7 : Stall Prevention Level During Run
8 : PID Feedback
9 : PID Target
10: Differential PID Feedback
11 : Overtorque/ Undertorque Detection
18: Communication Mode 1
19 : Communication Mode 2
20V/F separation voltage
Default: 0
Range: 0 to 20
E3-02<4>
Terminal A1
Input Gain
Sets the terminal A1 input gain as a
percentage when inputting 10V
Default: 100.0 %
Min.: -999.9 %
Max.: 999.9 %
E3-03<4>
Terminal A1
Input Voltage
Bias
Sets the terminal A1 input voltage bias as a
percentage when inputting 0V
Default: 0.0 %
Min.: -999.9 %
Max.: 999.9 %
E3-05
Terminal A1
Input Filter Time
Sets the terminal A1 primary delay filter time,
which can eliminate the interference
Default: 0.05 s
Min.: 0.00 s
Max.: 2.00 s
E3-06
Terminal A2
Signal Level
Selection
0 : 0 to 20 mA
1 : 4 to 20 mA
2 : 0 to 10 V
Default: 1
Range: 0 to 3

Other manuals for LiteOn EVO 6800 Series