10: Soft Starter Output Frequency
11 :Pulse Train Input
Sets the terminal AM gain.
Default: 100.0 %
Min.: -999.9 %
Max.: 999.9 %
Terminal AM
Monitor Voltage
Bias
Sets the terminal AM voltage bias.
Default: 0.0 %
Min.: -999.9 %
Max.: 999.9 %
E5:Pulse Train Input/ Output
Pulse Train Input
Function
Selection
Selects the function for terminal RP.
0 ∶Frequency Command
1 ∶ PID Feedback
2 ∶ PID Target
Default: 0
Range: 0, 1, 2
Pulse Train Input
Scaling
Sets the frequency equal to 100% frequency
in Hz.
Default: 1440 Hz
Min.: 100 Hz
Max.: 50000 Hz
Sets the level of the input gain to terminal RP.
Default: 100.0%
Min.: 0.0 %
Max.: 1000.0 %
Pulse Train Input
Voltage Bias
Sets the level of the input voltage bias when
no signal (0Hz) is input to terminal RP.
Default: 0.0%
Min.: -100.0
Max.: 100.0
Pulse Train Input
Filter Time
Sets the pulse train input primary filter time
in seconds.
Default: 0.10 s
Min.: 0.00 s
Max.: 2.00 s
Pulse Train Input
Minimum
Frequency
Sets the minimum frequency detected by the
pulse train input. Enabled when E5-00 = 0, 1,
2.
Default: 0.5 Hz
Min.: 0.1 Hz
Max.: 1000.0 Hz
Pulse Train
Monitor
Selection
Sets the function of pulse train output
terminal MP
0 : Frequency Command
1 : Output Frequency
2 : Soft Starter Output Frequency
3 : PID Feedback Value
4 : PID Target Value
Pulse Train
Monitor
Scaling
Sets the pulse train output frequency when
the specified monitor item is at 100%.
Default: 1440 Hz
Min.: 100 Hz
Max.: 50000 Hz
0:Pulse train input
1:PWM signal input