motor poles)
3 : Use user-defined units (defined by o1-02
and o1-03)
User-Defined
Frequency
Command
Setting/Display
Default: Determined
by o1-00
Min.: 1
Max.: 60000
Frequency
Command
Setting/Display
Decimal Places
Default: Determined
by o1-00
Min.: 0
Max.: 3
o2: Multi-Function Selection
LO/RE
(LOCAL/REMOTE
) Key Function
Selection
Enables or disables LO/RE key on the keypad.
0 ∶ Disabled
1 ∶ Enabled
Switches between Local and Remote
Operation
STOP Key
Function
Selection
Enables or disables the STOP key on the
keypad when the drive is controlled from a
remote source.
0 ∶ Disabled
1 ∶ Enabled
The STOP key always stops drive operation
even if the command source is not set to the
keypad.
Set this parameter after replacing the
terminal block or drive modules.
Default: <2>
Determined by
drive capacity
ENTER Key
Function During
Frequency
Command
Setting
0 ∶ ENTER Key Required
1 ∶ ENTER Key Not Required
After 5 second, the frequency is
automatically setting. When entering a
frequency command, the output frequency
changes immediately by UP or DOWN key
2 ∶ ENTER Key Not Required
After 1 second, the frequency is
automatically setting