EasyManua.ls Logo

LiteOn EVO 6800 Series - Page 120

LiteOn EVO 6800 Series
169 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
117
Parameter
Name
Description
Setting Range
Keypad
Disconnection
o2-06
Operation
Direction at
Power Up when
Using Keypad
0 Forward
1 Reverse
This parameter is enabled only when the
keypad is selected as the Run command
source.
Default: 0
Range: 0, 1
o4: Maintenance Settings
o4-00
Cumulative
Operation Time
Setting
Sets the initial value by 10 hours to start
keeping track of cumulative operation time.
Default: 0 h
Min.: 0 h
Max.: 6000 h
o4-01
Retain
o4-02
Cooling Fan
Operation Time
Setting
Sets the initial value to start keeping track of
cumulative fan operation time. View the
cumulative fan operation time in U3-01.
Default: 0 h
Min.: 0 h
Max.: 6000 h
o4-06
U2 Reset Setting
Resets the data for U2-□□ (Fault
Information) as these data will not be reset by
A1-03 (Reset).
0 Disabled
1 Enabled
Default: 0
Range: 0, 1
o4-07
kWh Monitor
Initialization
0U3-08 and U3-09 monitor data is not reset
when the drive is initialized.
1U3-08 and U3-09 monitor data is reset
when the drive is initialized.
Default: 0
Range: 0, 1
Group t, Auto-Tuning
t1: IM Motor Auto-Tuning
t1-01
Auto-Tuning
Method
Selection
0 Rotational Auto-Tuning
1 Stationary Auto-Tuning
2 Stationary Auto-Tuning for Line-to-Line
Resistance
Default 0
Min.: 0
Max.: 2
t1-02
Motor Output
Power
Sets the motor rated output power in kW
units.
Note: 1HP (Horse Power) = 0.746kW
Default depend on
o2-03A1-06
Min.: 0.00 kW
Max.: 650.00 kW
t1-03
Motor Rated
Voltage
Sets the motor rated voltage according to the
motor nameplate.
Default depend on
A1-06
Min.: 0.0 V
Max.: 255.0 V <3>