Operation
Direction at
Power Up when
Using Keypad
0 ∶ Forward
1 ∶ Reverse
This parameter is enabled only when the
keypad is selected as the Run command
source.
Cumulative
Operation Time
Setting
Sets the initial value by 10 hours to start
keeping track of cumulative operation time.
Default: 0 h
Min.: 0 h
Max.: 6000 h
Cooling Fan
Operation Time
Setting
Sets the initial value to start keeping track of
cumulative fan operation time. View the
cumulative fan operation time in U3-01.
Default: 0 h
Min.: 0 h
Max.: 6000 h
Resets the data for U2-□□ (Fault
Information) as these data will not be reset by
A1-03 (Reset).
0 ∶ Disabled
1 ∶ Enabled
kWh Monitor
Initialization
0:U3-08 and U3-09 monitor data is not reset
when the drive is initialized.
1:U3-08 and U3-09 monitor data is reset
when the drive is initialized.
Auto-Tuning
Method
Selection
0 ∶ Rotational Auto-Tuning
1 ∶ Stationary Auto-Tuning
2 ∶ Stationary Auto-Tuning for Line-to-Line
Resistance
Default∶ 0
Min.: 0
Max.: 2
Sets the motor rated output power in kW
units.
Note: 1HP (Horse Power) = 0.746kW
Default∶ depend on
o2-03,A1-06
Min.: 0.00 kW
Max.: 650.00 kW
Sets the motor rated voltage according to the
motor nameplate.
Default∶ depend on
A1-06
Min.: 0.0 V
Max.: 255.0 V <3>