118
Parameter
Name
Description
Setting Range
t1-04
Motor Rated
Current
Sets the motor rated current according to the
motor nameplate.
Default <2>
according to different
power inverters
Minimum value:
Inverter rating
Min.: 10% of drive
rated current
Max.:200% of drive
rated current
t1-05
Motor Base
Frequency
Sets the motor base frequency according to
the motor nameplate.
Default depend on
A1-03
Min.: 0.0 Hz
Max.: 400.0 Hz
t1-06
Number of
Motor Poles
Sets the number of motor poles according to
the motor nameplate.
Default 4
Min.: 2
Max.: 48
t1-07
Motor Base
Speed
Sets the motor base speed according to the
motor nameplate.
Default: depend on
A1-03
Min.: 0 rpm
Max.: 24000 rpm
t1-09
Motor No-Load
Current
(Stationary Auto-
Tuning)
Sets the no-load current for the motor.
After the motor output power and rated
current are set in t1-02 and t1-04, this
parameter will automatically display the no-
load current of a standard motor. The no-load
current must be entered according to the
motor test report.
Default
Determined by o2-
03A1-06
Min.: 0.0 A
Max.: t1-04
t1-12
Motor Auto-
Tuning Setting
Enables or disables Auto-Tuning when A1-
02=0 to 3
0 : Disabled
1 : Enabled
Default 0
Min.: 0
Max.: 1
Group F, Optional Function Group
F1: Pump function
F1-00
User pressure
sensor
specifications
Set according to the pressure sensor
specifications (the pressure value
corresponding to the maximum feedback
voltage or feedback current)
Default: 10.0
Min.: 0.1
Max.: 99.9
Unit: 0.1bar
F1-01
<9>
(Switch mode)
pressure
operation
interval
In switch mode, the inverter will automatically
control the pump according to the set value.
Start or stop.
Default: 5
Min.: 0
Max.: 100
Unit: 1%