119
6.5 Group d, Motor Parameters
d parameters set the V/F characteristics and motor parameters.
d1 V/F Characteristics
d1- 00 Input Voltage Setting
Sets this parameter to match the input voltage of the drive as the base for detections such as
ov (Overvoltage) and Uv (Undervoltage).
Notice: To ensure the drive protection functions work properly, always set the input voltage of the drive (not
motor) to this parameter. Failure to comply could cause damage to the machinery or injury to personnel.
<1> This is for a 200 V AC drive. The value is doubled for a 400 V AC drive.
□ Values Related to Drive Input Voltage
The following detection levels are determined by the drive input voltage.
P7-13
(DC Braking
Level) <1>
P2-08
(Voltage Target
During KEB)
P3-04
(Stall Prevention
Level during
Deceleration)
<1> The braking transistor operation level.
■ V/F Pattern Setting( d1-01)
The set V/F pattern determines the output voltage according to the frequency command.
There are 15 different preset V/F patterns (setting 0 to E: only the maximum voltage and base
voltage can be changed) and user-defined V/F patterns d1-02 to d1-11 (setting F).
d1- 01 V/F Pattern Selection
Selects 1 V/F pattern from the preset 15 ones or sets the user-defined V/F pattern.