159
15V
10V
5V
-5V
-10V
-15V
100%
Monitor value
-100%
When E4-00, E4-04 = 1
15V
10V
5V
-5V
-10V
-15V
-100%
When E4-00, E4-04 = 1
Output
voltage
10V
5V
0V
Monitor value
0% 100%
Gain 150%
Bian 0%
Gain 100%
Bias 0%
Gain 50%
Bias 0%
When E4-00, E4-04 = 0
10V
3V
0V
0% 100%
Gain 100%
Bias 30%
Gain 100%
Bias 0%
When E4-00, E4-04 = 0
Gain 150%
Bias 0%
Gain 100%
Bias 0%
Gain 50%
Bias 0%
Gain 100%
Bias 30%
Gain 100%
Bias 0%
Output
voltage
Output
voltage
Output
voltage
100%
Monitor value
Monitor value
Figure 6.69 Analog Output Gain and Bias Opeartion
.
Example 1: When E4-02 = 80% , the voltage output to terminal FM equals to 100% resulting 8
V.
Example 2: When E4-03 = 5% , the voltage output to terminal FM equals to 0% resulting 0.5 V.
E5 Pulse Train Input/ Output
A pulse train signal of maximum 32kHz frequency can input to terminal RP as frequency
command, PID control, PID target, or as the speed feedback in V/F Control method.
The pulse output monitor terminal MP can output drive monitor values as a pulse train signal
of maximum 32kHz frequency.
Set the scale and functions of the pulse input terminal RP and pulse output terminal MP by E5-
□□ as illustrated in Figure 6.70.