2.6 Common Specifications
V/F, Sensorless Voltage Vector Control (SVVC)
Digital Input: Within ±0.01% of the max. output frequency
Analog Input: Within ±0.1% of max. output frequency (-10℃ to
+50℃)
Frequency Setting
Resolution
Analog Output: 1/1000 of max. frequency
150% / 3Hz (V/F)
200% / 0.3Hz (IM Sensorless Voltage Vector Control)
1: 40 (V/F)
1:200 (IM Sensorless Voltage Vector Control)
Speed Control
Accuracy
*1
±0.2% (Sensorless Voltage Vector Control)
Over 5Hz (Sensorless Voltage Vector Control)
Options C2(<7.5kW), C3(>11KW)
15 fixed patterns and 1 programmable pattern
120% for 1 min. in every 10 min. (Normal Duty)
150% for 1 min. in every 10 min. (Heavy Duty)
180% for 10 sec.. in every 10 min. (Heavy Duty)
200% for 11 sec.. in every 10 min. (Heavy Duty)
Indoor without corrosive gas/liquid or flammable gas/liquid/oil
mist/dust
-10℃ to +50℃, -10℃ to +40℃ (NEMA1), below 90% RH without
froze or condensation